Replacement:
This part of IEC 61558 deals with the safety of
transformers for
construction sites and
power supply units incorporating
transformers for construction sites.
Transformers incorporating
electronic circuits are also
covered by this standard.
NOTE 1 Safety includes electrical, thermal and mechanical
aspects.
Unless otherwise specified, from here onward, the term
transformer covers transformers
for construction sites and power supply
units incorporating transformers for construction
sites.
This part is applicable to stationary or portable, single-phase
or polyphase, air-cooled (natural or forced)
independent or associated
transformers, being isolating or
safety isolating
dry-type transformers for the use
on construction sites. The windings may be
encapsulated or non-encapsulated.
The rated supply voltage does not exceed 1 000
V a.c., and the rated supply frequency and the
internal operating frequencies do not exceed 500
Hz.
This standard used in combination with Part 2-16 for
Switch mode power supply units (SMPS) is also
applicable to power supplies with internal
operating frequencies higher than 500 Hz. Where the two
requirements are in conflict the most severe take precedence The
rated output does not exceed:
– 25 kVA for single-phase transformers;
– 40 kVA for poly-phase transformers.
This part is applicable to transformers without limitation of
the rated output subject to an agreement between the purchaser and
the manufacturer.
NOTE 2 Transformers intended to supply
distribution networks are not included in the scope.
Isolating transformers and power supply units
incorporating isolating transformers for construction
sites have a no-load output voltage and a
rated output voltage exceeding 50 V a.c. and not
exceeding 250 V a.c.
Safety isolating transformers and power
supply units incorporating safety isolating
transformers for construction sites have a no-load
output voltage and a rated output voltage
not exceeding 50 V a.c.
NOTE 3 This standard is applicable to
transformers for the supply of electricity in
locations as specified in IEC 60364-7-704. The latter also
specifies the protection by using an earthed midpoint or starpoint
of the output winding.
Transformers and power
supply units covered by this part are used in
applications where it is required by the installation rules or by
the appliance specification for protection purposes. When the
transformers or power supply
units are incorporated into low
voltage switchgear and
controlgear assemblies for construction sites as specified
in IEC 60439- 4, the additional requirements of IEC 60439-4 will
apply to the assembly.
NOTE 4 For transformers filled with liquid
dielectric or pulverised material, such as sand, additional
requirements are under consideration.
NOTE 5 Attention is drawn to the following:
– measures to protect the enclosure and the
components inside the enclosure against external
influences like fungus, vermin, termites, solar-radiation and icing
should also be considered;
– the different conditions for transportation,
storage, and operation of the transformers and
power
supplyunits should also be
considered;ply units should also be considered;
– additional requirements in accordance with other appropriate
standards and national rules may be applicable to
transformers and power
supply units intended for use in special
environments such as tropical environment
NOTE 6 Future technological development of
transformers may necessitate a need to increase
the upper limit of the frequencies, until then this standard may be
used as a guidance document.