SAI AS/NZS 61000.2.4

SA ASNZS 6100024 2009-JUL-15 Electromagnetc compatblty EMC Part 24 Envronment—Compatblty levels n ndustral plants for low-frequency conducted dsturbances

More details

Download

PDF AVAILABLE FORMATS IMMEDIATE DOWNLOAD
$58.00 tax incl.

$116.00 tax incl.

(price reduced by 50 %)

1000 items in stock

This part of IEC 61000 is concerned with conducted disturbances in the frequency range from 0 kHz to 9 kHz. It gives numerical compatibility levels for industrial and non-public power distribution systems at nominal voltages up to 35 kV and a nominal frequency of 50 Hz or 60 Hz.

Power supply systems on ships, aircraft, offshore platforms and railways are not included.

The compatibility levels specified in this standard apply at the in-plant point of coupling. At the power input terminals of equipment receiving its supply from the above systems, the severity levels of the disturbances can, for the most part, be taken to be the same as the levels at the in-plant point of coupling. In some situations this is not so, particularly in the case of a long feeder dedicated to the supply of a particular load, or in the case of a disturbance generated or amplified within the installation of which the equipment forms a part.

Compatibility levels are specified for electromagnetic disturbances of the types which can be expected at any in-plant point of coupling (IPC) within industrial plants or other non-public networks, for guidance in

a) limits to be set for disturbance emission into industrial power supply systems (including the planning levels defined in 3.1.5);

NOTE 1 A very wide range of conditions is possible in the electromagnetic environments of industrial and other non-public networks. These are approximated in this standard by the three classes described in Clause 4. However, it is the responsibility of the operator of such a network to take account of the particular electromagnetic and economic conditions, including equipment characteristics, in setting the above mentioned limits.

b) the choice of immunity levels for the equipment within these systems.

The disturbance phenomena considered are:

– voltage deviations;

– voltage dips and short interruptions;

– voltage unbalance;

– power-frequency variations;

– harmonics up to order 50;

– interharmonics up to the 50th harmonic;

– voltage components at higher frequencies (above 50th harmonic);

– d.c. component;

– transient overvoltages.

The compatibility levels are given for different classes of the electromagnetic environment determined by the characteristics of the supply network.

NOTE 2 Compatibility levels at the point of common coupling (PCC) on public networks are specified in IEC 61000-2-2 for low-voltage networks and IEC 61000-2-12 for medium-voltage networks. Technical reports IEC 61000-3-6 and IEC 61000-3-7 describe the approach of supply authorities to the limitation of emissions from installations and large loads.